รายละเอียดสินค้า
เซนเซอร์วัดกระแสไฟฟ CT สำหรับ Power meter Three phase current transformer low voltage high accuracy D363 3*100/5A ความแม่นยำสูง
>> เช็คสต๊อคสินค้า <<
D363 Current transformer:
- Primary current: 3 X 50A-600A
 - Secondary current: 5A,1A
 - Standard approval: VDE0414,BS7626,IEC60044-1
 - Maximum voltage: 0.72/3KV
 - Frequency: 50-60Hz
 - Rated load: 1.25VA—5VA
 - Class: 1.0
 - Short-time thermal current: Ith=60×Ih
 - Rated security coefficient: FS<5
 
Technical data:
| Model | 
 Ratio  | 
Rated Burden (VA) | 
 class  | 
 Rated  | 
Rated Frequency  | 
| 
  D363 
 | 
  3*50/5A 
 | 
  1.25VA 
 | 
  3 
 | 
  0.72KV 
 | 
  50/60Hz 
 | 
| D363 | 3*75/5A | 1.5VA | 3 | 0.72KV | 50/60Hz | 
| D363 | 3*100/5A | 2.5VA | 1 | 0.72KV | 50/60Hz | 
| D363 | 3*150/5A | 2.5VA | 1 | 0.72KV | 50/60Hz | 
| D363 | 3*200/5A | 2.5VA | 0.5 | 0.72KV | 50/60Hz | 
| D363 | 3*250/5A | 5VA | 0.5 | 0.72KV | 50/60Hz | 
| D363 | 3*300/5A | 5VA | 0.5 | 0.72KV | 50/60Hz | 
| D363 | 3*400/5A | 5VA | 0.5 | 0.72KV | 50/60Hz | 
| D363 | 3*500/5A | 5VA | 0.5 | 0.72KV | 50/60Hz | 
| 
 Model  | 
 A  | 
 B  | 
 C  | 
 D  | 
 E  | 
 F  | 
 G  | 
| 
 D363 
 | 
 185 
 | 
 84 
 | 
 27 
 | 
 75 
 | 
 87 
 | 
 61 
 | 
 41 
 | 
รับประกันสินค้า 6 เดือน













		
		
		